Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR |
| 08/09/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*THE 1999 NATL. ELECTL CODE ART 250-84 REQUIRES THE GAS AND WATER PIPING ALSO BE GROUND BONDED TO THE UFER OF THE MAIN PANEL OR THEY MAY BE RUN SEPARATELY. THE USE OF KEARNEY SPLICE BOLTS IS PROHIBITED ON THE GROUNDING CONDUCTOR. CAD WELD OR IRREVERSIBLE CRIMP LUGS ARE THE ONLY METHODS ALLOWED. CORRECT & RECALL, THANKS ALSO IDENTIFY YOUR CIRCUIT BREAKERS AND INSTALL A PERMANENT LABEL ADDRESS ON YOUR METER SECTION. NO "MAGIC MARKERS" ALLOWED. |