Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02049

Parcel: 130082140


Addresses:

3601 E 27TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/10/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR
08/09/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*THE 1999 NATL. ELECTL CODE ART 250-84 REQUIRES THE GAS AND WATER PIPING ALSO BE GROUND BONDED TO THE UFER OF THE MAIN PANEL OR THEY MAY BE RUN SEPARATELY. THE USE OF KEARNEY SPLICE BOLTS IS PROHIBITED ON THE GROUNDING CONDUCTOR. CAD WELD OR IRREVERSIBLE CRIMP LUGS ARE THE ONLY METHODS ALLOWED. CORRECT & RECALL, THANKS ALSO IDENTIFY YOUR CIRCUIT BREAKERS AND INSTALL A PERMANENT LABEL ADDRESS ON YOUR METER SECTION. NO "MAGIC MARKERS" ALLOWED.