Permit: T01EL02048

Parcel: 10706100A

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/13/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) BOND DEVICE NEEDED AT CONCETRIC FOR METER SOCKET 2ND BLDG. 2.) BOND ENCLOUSER 2ND BUILDING 3.) DOUBLE LUGGING BOTH BUILDING DISCONNECT 4.) DOUBLE LUGGING GUTTER 2ND BUILDING 5.) IDENTIFICATION OF FEEDERS 225-37 6.) ACCESSIBILITY OF SERVICE 240-24 (6) OK TO CLEAR POWER LEFT VOICE MAIL
08/12/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) NEED ADDRESSING ON BUILDING AS PER CODE 2.) DOUBLE LUGING AT DISCONNECT. 3.) NEED GROUNDING INSTALL BEFORE POWER RELEASE 4.) VERIFY WATER AND GAS BONDING 5.) PLEASE PROVIDE A PLAN AS TO WHAT EACH SERUCE IS FEEDING 6.) WHY DO WE HAVE DIFFERENT ADDRESS