Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02034
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR. | |
| 08/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*NOTES: STILL NO COMPLIANCE WITH ITEM #1 LAST INSPECTION. A RE-INSPECTION FEE IS ASSESED PAY RE-FEE 201 N STONE PRIOR TO CALLING FOR FURTHER INSPECTIONS. | |
| 08/22/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) INSTALL EQUIP. BONDING JUMPERS ON GROUND BUSHINGS 250 N.E.C. 2.) NO COMPLIANCE WITH #6 (ITEM LAST INSP. WRITE UP.) 3.) USE PROPER KO PLUG LISTED FOR OUTDOOR. USE 110-3 NEC 110-12 4.) I.D. CIRCUIT BREAKERS. | |
| 08/13/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) NO CHASE NIPPLE 250-94 NEC. 2.) BOND BUSHINGS REQUIRED OR BONDING LOCKNUTS IN GUTTER ON 2" NIPPLES 250-94 3.) INSTALL GROUND LUGS IN GUTTER AND BOND EQUIPMENT GROUNDS PROPERLY PER ART 250 NEC. 4.) REMOVE WATER AND GAS BOND WIRE OFF THE NEUTRAILS IN GUTTER AND ATTACH TO GROUND LUG IN GUTTER 250-104. 5.) BOND J BOXES & USE W/P KO SEAL. ART 110-3, 110-12 NEC. 6.) PROVIDE BRACING TO KEEP CONDUCTORS FROM PUSHING AGAINST GUTTER COVER 110-12 NEC. |