Permit: T01EL02034

Parcel: 122123060


Addresses:

1621 N VENICE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02034

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR.
08/28/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*NOTES: STILL NO COMPLIANCE WITH ITEM #1 LAST INSPECTION. A RE-INSPECTION FEE IS ASSESED PAY RE-FEE 201 N STONE PRIOR TO CALLING FOR FURTHER INSPECTIONS.
08/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) INSTALL EQUIP. BONDING JUMPERS ON GROUND BUSHINGS 250 N.E.C. 2.) NO COMPLIANCE WITH #6 (ITEM LAST INSP. WRITE UP.) 3.) USE PROPER KO PLUG LISTED FOR OUTDOOR. USE 110-3 NEC 110-12 4.) I.D. CIRCUIT BREAKERS.
08/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) NO CHASE NIPPLE 250-94 NEC. 2.) BOND BUSHINGS REQUIRED OR BONDING LOCKNUTS IN GUTTER ON 2" NIPPLES 250-94 3.) INSTALL GROUND LUGS IN GUTTER AND BOND EQUIPMENT GROUNDS PROPERLY PER ART 250 NEC. 4.) REMOVE WATER AND GAS BOND WIRE OFF THE NEUTRAILS IN GUTTER AND ATTACH TO GROUND LUG IN GUTTER 250-104. 5.) BOND J BOXES & USE W/P KO SEAL. ART 110-3, 110-12 NEC. 6.) PROVIDE BRACING TO KEEP CONDUCTORS FROM PUSHING AGAINST GUTTER COVER 110-12 NEC.