Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*ADDRESS PER CITY AMMEND. NEED WATER/GAS BOND. BURRY GROUND WIRE DRIVE ROD FLUSH, OTHER ROD CUT NEED LETTER FROM C-11 THAT SAID COMPANY IS RESPONSIBLE AND DOING WORK HOUSE REWIRED NEW HOOD WIRING SOME GROUND WIRE CUT NEW PLUMBING NEW DRYWALL NEW HVAC NEED ACURATE CITY APPROVED PLANS OPEN PER GENERAL INSPECTOR REQUIREMENT. |
| 09/04/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/28/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*DENIED COMPLETE GROUNDING NEED TO SEE INTERIOR TERMINATION ADDRESS PER CITY RISER NEEDS STRAP.AND LEAVE NAME OF LICENSED C-11 CONTRACTOR BEFORE NEXT. |