Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/05/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP.
11/01/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) RISER SUPPORT SCREWS NOT SEATED PROPERLY. SEE ITEMS. #4.
08/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) INSTALL BOND BUSHINGS ON CONNECTORS USING CONCENTRIC KO'S AND FEEDER CONDUITS, PER ART 250 N.E.C. 2.) INSTALL CONNECTOR WITH BUSHING WHERE CABLE EXITS CONDUIT SLEEVE. PER ART 300 N.E.C. 3.) BOND GAS PIPE PER 250 N.E.C. 4.)SUPPORT RISER CONDUIT WITH MIN 1/4" BOLTS N.E.C. 110-12 ALSO RISERS OVER 2" ABOVE ROOF REQUIRE BRACING. 5.) LOCATE AND EXPOSE TOPS OF GROUND RODS FOR INSP.