Permit: T01EL01971

Parcel: 120082880


Addresses:

207 W OHIO ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T01EL01971

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2001 ELECTRIC - RECONNECT Approved
10/18/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*YOU HAVE NOT COMPLIED WITH THE LAST WRITE UP A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTOR.
09/28/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*DENIED A RE-INSPECTION FEE IS DUE. 1.) 2X4 TO SUPPORT RISER NOT EFFECTIVE 2.) NEED FILLER PLATES FOR DEAD FRONT COVER. 3.) WIRING TO REAR NOT DISCONNECTED 4.)NEW FURNACE INSTALLATION PERMIT. 5.) NEED TO SEE REAR UNIT. 6.) NEED PERMANENT ADDRESS A
07/27/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) SEAL HOLE BOTTOM OF SERVICE 2.) SEAL TOP HOLE OF BOX TO RIGHT OF PANEL 3.) #12 WIRE GOOD FOR ONLY 20AMPS IS DOUBLE LUGGED ON 50 AMP CIRCUIT BREAKER. 4.) ALL CONDUITS GOING TO SERVICE NEED TO BE SUPPORTED WITHIN 3' OF SERVICE 5.) INSTALL A 2 X 4 PEICE OF WOOD TO SUPPORT RISER IT NEEDS TO HAVE 2 SUPPORTS ONLY HAS ONE 6.) WIRING IN REAR TO BE DISCONNECTED. 7.) EAST ROOM INSTALL LIGHT FIXTURE & COVER PLATES APPEARS TO BE A RECENT ADDITION WAS PERMIT OBTAINED OR ADDITION CHECKED IF NOT PLEASE DO SO 8.) SMOKE DETECTORS REQUIRED IN BEDROOMS CALLED OFFICE TO SEE A PERMIT HAD BEEN PREVIOUSLY BEEN TAKEN OUT FOR ADDITION NONE ON RECORD.