Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T01EL01971
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2001 | ELECTRIC - RECONNECT | Approved | ||
| 10/18/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*YOU HAVE NOT COMPLIED WITH THE LAST WRITE UP A RE-INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTOR. | |
| 09/28/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*DENIED A RE-INSPECTION FEE IS DUE. 1.) 2X4 TO SUPPORT RISER NOT EFFECTIVE 2.) NEED FILLER PLATES FOR DEAD FRONT COVER. 3.) WIRING TO REAR NOT DISCONNECTED 4.)NEW FURNACE INSTALLATION PERMIT. 5.) NEED TO SEE REAR UNIT. 6.) NEED PERMANENT ADDRESS A | |
| 07/27/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) SEAL HOLE BOTTOM OF SERVICE 2.) SEAL TOP HOLE OF BOX TO RIGHT OF PANEL 3.) #12 WIRE GOOD FOR ONLY 20AMPS IS DOUBLE LUGGED ON 50 AMP CIRCUIT BREAKER. 4.) ALL CONDUITS GOING TO SERVICE NEED TO BE SUPPORTED WITHIN 3' OF SERVICE 5.) INSTALL A 2 X 4 PEICE OF WOOD TO SUPPORT RISER IT NEEDS TO HAVE 2 SUPPORTS ONLY HAS ONE 6.) WIRING IN REAR TO BE DISCONNECTED. 7.) EAST ROOM INSTALL LIGHT FIXTURE & COVER PLATES APPEARS TO BE A RECENT ADDITION WAS PERMIT OBTAINED OR ADDITION CHECKED IF NOT PLEASE DO SO 8.) SMOKE DETECTORS REQUIRED IN BEDROOMS CALLED OFFICE TO SEE A PERMIT HAD BEEN PREVIOUSLY BEEN TAKEN OUT FOR ADDITION NONE ON RECORD. |