Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/27/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR |
| 07/24/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABEL, SCREWED OR RIVITED TO SERVICE ENCLOSURE 230-70 N.E.C. #9287 CITY ORDIN. 2.) INSTALL BOND BUSHINGS ON FEEDER CONDUIT CONNECTORS 250-94 N.E.C. 3.) SEALING LOCKNUT OR HUB REQUIRED ON CONDUIT CONNECTOR AT TOP OF PANEL AND BOND BUSHING 250-94 N.E.C. 4.) FEEDER FOR GUEST HOUSE TO BE PROTECTRED ENTIRE RUN OUTSIDE OF STRUCTURE 373-2,300-15C 300-16 N.E.C. 5.) WRAP SPLIT BOLTS IN GUTTER TO EQUAL INSULATION OF CONDUCTORS BEING SPLICED. 110-14 N.E.C. 6.) USE 1/4" MIN ANCHOR BOLTS FOR RISER, 110-3 110-12 N.E.C. 7.) BOND GAS LINES 250-140 N.E.C. 8.) INSTALL GROUND LUG IN GUTTER NEC 250-148 |