Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/17/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RE-CONN T.E.P. WILL BE NOTIFIED BY CITY FOR RE-CONN OF POWER. |
| 07/24/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*TOO MANY PROBLEMS OBTAIN A LICENSED ELECTRICIAN WITH L-11 LICENSE TO REPAIR AND RECALL INSPECTION. 1.) BLANK OFF OR INSTALL FIXTURES MID LARGE ROOM 2 OPEN BOXES. 2.) SWITCH MISSING BACK STORAGE ROOM NO SWITCH OR PLATE. 3.) LIGHT IMPROPERLY HUNG AND MISSING RECEPTACLE COVER IN ROOM TO EAST OR #2. 4.) ROOM SOUTH OR #3 LIGHT IMPROPERLY CONNECTED. 5.) ROOM EAST OR #4 LIGHT IMPROPERLY CONNECTED. INSTALL PROPER TYPE PROCELAIN HOLDER WITH PULL CHAIN OK 6.) ROMEX CABLE FEED J-BOX IN YELLOW SHELF (MIDDLE) HAS TO BE PROTECTIES PHYSICALLY. 7.) OUTSIDE RECEPTACLE OR J-BOX NOT ATTACHED TO WALL SHOWING WIRE, ALSO SUPPORT PIPE. 8.) ROOF WIRING NEEDS TO BE CLEANED UP, CLOSE BOXES SECURE CONDUIT ETC NOT ON TOP OF 2 X 4 WOOD.9.) SEAL HOLE BOTTOM OF SERVICE PANEL, ONE BREAKER BOTTOM ONE NOT RIGHT KIND. 10.) UNPROTECTED ROMEX COMING OUT OF SERVICE #12 COPPER ON 30 AMP CB. 11.) IN PANEL #12 COPPER ON 30 A CIRCUIT BREAKER. |