Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/04/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 08/01/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*NO WORK PROGRESS BOND CONDUCTOR: NOW NOT CONNECTED AT SUBPANEL A REFEE HAS BEEN ASSESSED. |
| 07/25/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SERVICES NEED TO BE BONDED TOGETHER 250-58 2.) CAN NOT USE SHEET METAL SCREW 250-8 |
| 07/22/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) BOND BOTH SERVICES TOGETHER #1 & #2 2.) CLEAN SURFACE UNDER LUG 250-12 3.) CAN NOT USE SHEET METAL SCREW 250-8 4.) DOUBLE LUGING AT BOND BUSHING 5.) SEAL AT LB'S ENTERING HOUSE 6.) LABEL SUB PANEL. OK TO COVER TRENCH. |