Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR SERVICE. |
| 07/27/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) AT SERVICE THE #4 COPPER FROM THE GROUND RODS MUST BE TIED TO NEUTRAL BAR OR RUN #4 COPPER JUMPER BETWEEN NEUTRAL AND GROUND BAR IN CAN.2.) 2" EMT BELOW SERVICE NEED A GROUND BUSHING STANDARD LOCK NUT IS NOT SUFFICIENT 99 NEC 250-94. 3.) 1999 NEC 250:32-C WHERE AN EQUIPMENT GROUND IS NOT RUN TO SECOND BUILDING THE GROUND FROM RODS AND THE NEUTRAL ARE TO BE TIED TOGETHER. |