Permit: T01EL01879

Parcel: 117082480


Addresses:

942 S 5TH AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*FINAL OK TO CLEAR SERVICE
07/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) THE NEUTRAL AND THE # 4 COPPER FROM GROUND RODS NEED TO BE TIED TOGETHER RUN A JUMPER FROM NEUTRAL TO GROUND BAR. 2.) THE OLD SERVICE IS BEING USED IN AN UNAPPROVED MANNER. THE JUMPERS ARE TEMPORARY AND THE LOWER COMPARTMENT HAS HAD A NEUTRAL BLOCK MOUNNTED USE A PROPER TYPE PANEL AS ON 2ND STRUCTURE.