Permit: T01EL01866

Parcel: 126134060


Addresses:

4552 E 19TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/20/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR RECONNECT ADDRESS & J X BOX WIRES.
07/18/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) INSIDE PANEL HAS AN EAGLE TAP ON BUS TO FEED DRY SW UNPROTECTED #12 ON 60AMP BUS ROMEX. TO DRYER RUN THUR OPEN HOLE NO CLAMP. 2.) DRYER SW HAS #12'S ON 30 A BREAKER #' 12'S ONLY GOOD FOR 20 AMPS ROMEX TO DRYER SW NOT CLAMPED. 3.) REPLACE BROKEN RECEPTACLE SW BED ROOM 4.) INSTALL BATTERY IN SMOKE DETECTOR. 5.) OPEN WIRING METHODS TO CARPORT NOT APPROVED CORRECT OR REMOVE 6.) ADDRESS SERVICE.