Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01EL01828
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
| 09/17/2001 | SIGN ELECTRIC | Partial Approval | COMPLETE ALL ELECTRICAL TO INCLUDED ANY FRAME NEON. SIGN INSPECTOR WILL VERIFY SUITABILITY OF BOOTS TO EXPOSED EXTERIOR CONDITION PROVIDE THIS INFORMATION UPON NEXT INSPECTIONS. COMPLY AND RECALL INSPECTION. | |
| 09/11/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*OFFICE CLOSED @ 8:30 AM I NEED TO SEE PLANS & PERMITS.1.) EXPOSED BOOTS ON DOUBLE BACKS MUST BE LISTED FOR EXPOSED, DAMP LOCATION 2.) TAIL PIECES OF EXPOSED NEON WITH DOUBLE BACKS MUST BE FORMED SO THAT CONDENSATION WILL DRAIN OUT OF BOOT. | |
| 07/18/2001 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000* |