Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/23/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NOTES: OK CABLE DROP, OK TO CLEAR TEMP POWER. 1. SCREW MISSING ON CONNECTOR AT SUB PANEL BACK UNIT. ALSO BREAKERS NOT I.D.'ED. 2. PERMIT REQUIRED FOR NEW IINTERIOR WIRING OF UNIT IN BACK. 3. I.D. TAG ON BACK UNIT PANEL REQUIRED. 4. RECALL FOR FINAL AFRER POWER TIE IN. 5. OBTAIN PERMIT & CALL INSPECTIONS FOR NEW WIRING INTERIOR (UNIT IN BACK). |
| 07/24/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL BOND BUSHINGS ON RISER CONDUIT AND U.G. FEEDER CONDUIT. 250-94 N.E.C. 2.) USE MIN 1/4" BOLTS TO ANCHOR RISER CONDUIT NO DRYWALL SCREWS. 110-3,110-12 N.E.C. 3.) VERIFY WATER BOND. |