Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01824
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP SEVICE # B | |
07/24/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) CHASE NIPPLE NOT APPROVED WIRING METHOD 250-94 N.E.C. 2.) NEUTRAL OR GROUND CONDUCTOR MUST BE INDENTIFIED PER ART 200 OR 250 N.E.C. 3.) NEED TO VERIFY GROUND RODS,? 4.)NEED TO VERIFY GAS & WATER BONDS 250-104 N.E.C. 5.) ALL CIRCUIT BREAKER TO BE OF SAME MANUF.AS SERVICE CO. 110-3 N.E.C. |