Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2002 |
ELECTRIC - SERVICE RELOCATION |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE CALL FOR FINAL WHEN READY |
| 03/13/2002 |
ELECTRIC - SERVICE RELOCATION |
|
Partial Approval |
IVRS - Inspection 0000* NOW YOU NEED A GROUNDING BUSHING AND BONDING JUMPER AT RISER. OTHER ITEMS PLEASE GET A LICENSED CONTRACTOR. A REFEE IS DUE BEFORE THE NEXT INSPECTION. |
| 03/06/2002 |
ELECTRIC - SERVICE RELOCATION |
|
Denied |
IVRS - Inspection 0999*GROUNDING NOT PER CODE RODS TO BE 6' APART & OTHER ITEM. |