Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL01816

Parcel: 122160640


Addresses:

2225 N DODGE BL #02

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
07/24/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
07/13/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0245*1.) EXPOSED WIRING IN BACK AND SOUTH SIDE OF HOUSE UNDER 8' TO BE IN CONDUIT. SPLICES NEED TO BE IN W/P BOX WIRING OUTSIDE NEEDS TO BE TYPE UF OR IN CONDUIT. 2.) INSTALL SMOKE DETECTOR IN BEDROOM. 3.) NO GROUND SYSTEM IN BLD, INSTALL GROUND EQUIPMENT GROUND OR GFCI AHEAD OF OUTLET CIRCUITS.