Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2001 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 07/13/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0245*1.) EXPOSED WIRING IN BACK AND SOUTH SIDE OF HOUSE UNDER 8' TO BE IN CONDUIT. SPLICES NEED TO BE IN W/P BOX WIRING OUTSIDE NEEDS TO BE TYPE UF OR IN CONDUIT. 2.) INSTALL SMOKE DETECTOR IN BEDROOM. 3.) NO GROUND SYSTEM IN BLD, INSTALL GROUND EQUIPMENT GROUND OR GFCI AHEAD OF OUTLET CIRCUITS. |