Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL01808

Parcel: 132170500


Addresses:

1110 E OHIO ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/27/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/17/2001 ELECTRIC - FINAL Denied CANNOT DOUBLE LUG NUETRAL WIRE FROM HOUSE FEEDER. MAKE PROPER SPLICE NEED WATER AND GAS BOND NEED PERMANENT ADDRESS TAG WATER LINE SUBJOCENT TO SERVICE IS INPROPER.