Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2002 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RECONNECT ALL CORRECTION PER THOMAS LOWE'S ELECTIRCAL |
| 12/07/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) SERVICE NEEDS UPGRADE SERVICE HAS BEEN REPLACES, NON RAIN TIGHT, DOUBLE LUGGING AND EXCEDES MAXIMUM HEIGHT REURIREMENTS WILL NEED A COMPLETE GROUNDING ELECTRODE SYSTEM. 2.) A NEW ADDITION HAS BEEN BUILT WILL NEED TO SEE APP CITY APPROVED PLANS AND INSPECTIONS APPROVAL IF THE ABOVE #2 HAS NOT BEEN DONE AN ARCHITECT TO DRAW PLANS FOR THIS COMPLETE PROJECT. ELECTRICAL, MECHANCIAL BUILDING AND PLUMBING INVERSTIGATION FEES APPLICABLE. 3.) USING ZIP CORD IN BEDROOM WALLS & FLOOR 4.) INSTALL GFCI PROTECTION IN KITCHEN 5.) NEED SMOKE DETECTOR IN HALLWYA 6.) NEED TO REPAIR BROKEN RECEPTACLE IN OTHER BI |