Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CAN NOT ACCESS METER CAN AT THIS TIME. TEP ENERGIZED WITHOUT CLEARENCE. 2.) FINISH CIRCLED ITEMS ABOVE. ALSO I CAN NOT VERIFY IF ALLUNCIRCED WERE CORRECTED 3.) PLEASE HAVE APPROVED PLANS ON SITE. |
| 07/15/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NEED A SET OF PLANS APPROVED BY THE CITY OF TUCSON FOR ALL WORK IN PROGRESS. NEED TO REFLECT SERVICE, SUBPANEL AND NEW DISSCONNECTS TO EQUIPMENT, NEED CONDUIT SIZES & CONDUCTORS NEED FUSE RATINGS FOR FAULT CURRENT. 2.) LABELS DICONNECTS AND PANELS. 3.) CANNOT STACK LUGS. 4.) CLEAN FULL SURFACE UNDER LUG. 5.) LOOSE CONDUCTOR TERMANAL 6.) GROUNDING ELECTRODE SYSTEM TO BE INSTALLED AND UNSPLICED. 7.) BOND NEUTRAL TO GROUNDING ELECTRODE SYSTEM 250-24(A) (4) 8.) STRAP GROUND CONDUCTOR. 9.) TIGHTEN LOCK NUTS AT K-4 10.) SUPPORT CONDUITS AS PER CODE AND TIGHTEN FITTINGS 11.) LABEL BREAKERS 12.) PLEASE LEAVE OUTDOOR PANEL ACCESSABLE. |