Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL01789

Parcel: 12007405A


Addresses:

4314 S BELMAR AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/16/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
11/06/2001 ELECTRIC - SERVICE UPGRADE Denied 1.) NEED PERMANENT METAL ADDRESS TAG 2.) RODE TO BE 6FT APORT.
07/15/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) NEED PEMANENT METAL ADDRESS LABEL 2.) LABEL BREAKER 3.) CANNOT LOCATE 2ND GROUND ROD. 4.) USE CABLES RATED FOR BURIAL 5.) CANNOT USE SHEET METAL SCREWS FOR THE GROUND BAR 6.) BOND GROUND TO NEUTRAL AT SERVICE.