Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*1.) WE HAVE LOOSE CONDUIT FITTINGS. ALSO STRAP CONDUITS AS PER CODE. 2.) THE GARDEN HAS BEEN GROWN AGAIN IN FRONT OF SERVICE THIS A VIOLATION OF WORKING CLEARENCES 110-26. 3.) ITEMS #3 THE CONNECTOR FOR THE BOX BELOW THE PANEL CAN NOT BE A CHASE NIPPLE. 110-3. 4.) BOTH GAS SERVICE NEED TO BE BONDED 250-104. DUE TO ADMINSTRATIVE CODES THIS IS THE THIRD INSPECTION AND ALL WORK HAS NOT BEEN COMPLETED A REFEE IS BEING ASSESSED. |