Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0935* |
| 10/18/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) BOND BOTH INTERIOR GAS PIPINGS 2.) VERIFY WATER BOND. 3.) FINISH PREVIOUS INSPECTION DISCREPENCIES #3,5,6, |
| 07/19/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) NEED WORKING CLEARANCE IN FRONT OF PANEL 110-26 2.) NEED PERMANENT METAL ADDRESS LABELS 3.) USE APPROVED FITTING TO LB & BELL BOX CHASE NIPPLE NOT APPROVED. 4.) VERIFY SECOND GROUND ROD 5.) NEED GAS BOND. 6.) PLEASE IDENTIFY NEUTRAL CLOSER TO WETHER HEAD. |