Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0935* | |
10/18/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1.) VERIFY WATER BOND.2.) FINISH PREVIOUS INSPECTION DISCREPENCIES #3 & 7. | |
07/19/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1.) NEED WORKING CLEARENCE IN FRONT OF PANEL 110-26 2.) NEED PERMANENT METAL ADDRESS LABEL. 3.) USE APPROVED FITTING TO LB CHASE NIPPLE NOT APPROVED 4.) SECURE PANEL TO WALL 5.) VERIFY SECOND GROUND ROD 6.) NEED GAS BOND. 7.) PLEASE IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHER HEAD. |