Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01EL01785

Parcel: 124060230


Addresses:

828 E 7TH ST #02


Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T01EL01785

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
04/16/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0935*
10/18/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) VERIFY WATER BOND.2.) FINISH PREVIOUS INSPECTION DISCREPENCIES #3 & 7.
07/19/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) NEED WORKING CLEARENCE IN FRONT OF PANEL 110-26 2.) NEED PERMANENT METAL ADDRESS LABEL. 3.) USE APPROVED FITTING TO LB CHASE NIPPLE NOT APPROVED 4.) SECURE PANEL TO WALL 5.) VERIFY SECOND GROUND ROD 6.) NEED GAS BOND. 7.) PLEASE IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHER HEAD.