Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL01748
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/19/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PLEASE VERIFY GAS BOND. 2.) USE 1/4 " HARDWARE MINIMUM ON RISER SUPPORT 3.) LOOSE CONDUIT FITTINGS 4.) LABEL ALL BREAKERS 5.) JUNCTION TO CONVENT TO 120V SHOULD BE MADE IN JUNCTION BOX NOT PANEL 6.) USE CORRECT BREAKER FOR SUB PANEL 7.) CHECK AMPACITY OF CONDUCTOR TO SUBPANEL *NOTE SUB PANEL RATED 70A 120V A/C |