Permit: T01EL01726

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
09/19/2001 SIGN ELECTRIC Approved IVRS - Inspection 0000*
07/25/2001 SIGN ELECTRIC Denied IVRS - Inspection 0999*1.) MANUFACTURES SPECIFICATIONS REQUIRE TRANSFORMERS TO BE DIRECTLY WIRED TO EQUIPMENT GROUNDING CONDUCTOR (ATTACH GREEN WIRE TO TRANSFORMER, NOT JUST CAN) 2.) WHERE P.K. HOUSINGS ARE DRILLED INTO STUDS THE STUD WILL HAVE TO BE MOVED TO PROVIDE PROPER CLEARANCE FOR P.K. 3.) 1/2" FLEXIBLE CONDUIT WILL HAVE TO BE SECURELY ATTACHED TO P.K. BOTH P.K. THAT ARE IN STUDS. 4.) IDENTIFY SIGN CIRCUIT AT BREAKER PANEL.
07/23/2001 SIGN ELECTRIC Denied IVRS - Inspection 0999*IDENTIFY SIGN CIRCUIT