Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*LETTER RECEIVED FROM PYRAMID ELECT C-11 11633. CONTRACTOR TO COMPLETE SWITCH OVER ONCE SERVICE ENERGIZED BY TEP. |
| 03/19/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935* |
| 09/24/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 07/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NEED GAS BOND 2.) CLEAN SURFACE UNDER WATER BOND. 3.) NEED PERMENT METAL ADDRESS LABEL 4.) FILL UNUSED OPENING IN PANEL 5.) USE APPROVED METHOD FOR POWER TO SECOND BUILDING 6.) EXPOSED AND UNSAFE ROMEX TO EXISTING SERVICE. 7.) BOND BOTH SERVICE TOGETHER AS PER CODE. 8.) VERIFY LICENSED ELECTRIAL CONTRACTOR 9.) VERIFY PERMITS AND PAPER WORK FOR 2ND BUILDING |