Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*LETTER RECEIVED FROM PYRAMID ELECT C-11 118633. CONTRACTOR TO COMPLETE SWITCH OVER ONCE SERVICE ENERGIZED BY TEP. |
| 03/19/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0935* PLEASE CONTACT INSPECTOR CO MACHO 349-5842. NO WORK PROGRESS A REFEE HAS BEEN ASSESSED. |
| 03/05/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) CONDUCTOR TO HAVE MARKING AS PER CODE 310-8 & 310-11 ALSO SUPPORT IS NEEDED PER 225-6. 2.) PLEASE TERMANATE SERVICE DROP CONDUCTORS CORRECTLY 110-14. 3.) RISER SUPPORT TO USE 1/2" MININUM HARDWARE FOR SUPPORTS 4.) RISER USE FOR ARIAL SUPPORT OF CONDUCTORS NEED TO BE SUPPORTED. PLEASE PROVIDE A GUY BACK BRACE. 5.) PLEASE SUPPORT WETHERHEAD AND CONDUIT AT 2ND HOUSE 6.) VERIFY DISCONNECTING MEANS AT 2ND STRUCTURE 225-32. |
| 09/24/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*NEED TO OBTAIN LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK ON THESE RENTAL UNITS. CLEAN SURFACE FOR GAS BOND. |