Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/14/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS LABEL. 2.) 2 GROUND RODS ARE NEEDED 6' APART. 3.) USE #4 BARE COPPER IF EXPOSED 4.) LABEL BREAKERS 5.) USE APPROVED FITTINGS AT LB -CHASE NIPPLES NOT APPROVED 6.) NEED TO SEE CONDUIT SYSTEM TO SUB PANEL 7.) USE 1/4" HARDWARE MININUM ON RISER 8.) BOND GAS AND WATER. |