Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RECONNECT WILL NOTIFY TEP |
| 06/29/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
PLEASE CALL MIKE AT 440-7252 1/2 HR PRIOR TO INSPECTION. 1.) 50 AMP CIRCUIT BEAKER IN PANEL (MAIN) SHOULD BE 30 AMPS, ONLY #10 WIRE ON IT WHICH IS GOOD FOR 30 AMPS ONLY. TAPE GREEN WIRE GOING INTO BREAKER BLACK 2.) ISOLATE GROUNDS & NEUTRALS AT SUB PANEL ON SIDE ON HOUGHE. |