Permit: T01EL01639

Parcel: 13012011A


Addresses:

2110 S ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR SERVICE INCREASE.
06/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*WILLIAMSON HEATING & COOLING CALLED LEFT MESSAGE 9 AM PRIVATE EYE TATOO 2108 ADVANCED TRAN 2112 1.)THIS IS NOT A 400A SERVICE 3/0 COPPERS IN RISER LIMIT TO 200 AMP 2.) 200A FUSED DISCONNECT SHOULD HAVE FUSING REDUCED TO PROTECT CONDUCTORS GOING TO SUB-PANEL CANNOT READ SIZE BUT NOT 3/0'S 3.) FITTING GOING ABOVE PANEL (MIDDLE ONE IS REQUIRED TO HAVE LOCK NUT MADE UP ALL THE WAY. 4.) CHANGE NIPPLES USED ON BOTH LB FITTINGS COMING INTO 200AMP PANEL NOT ALLOWED FOR THIS USE NEED TO USE A CLOSED NIPPLE WITH LOCK NUTS ON EACH SIDE 5.) FOLD CONDUCTOR IN 200 PNL BACK COULD NOT REJECTED PUT COVER IN FREELY.PRIVATE EYE