Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL01631

Parcel: 110080380

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABELS PER 230-7 N.E.C. AND 9287 CITY OF TUCSON ORDIN. 2.) USE U.L. LISTED SPLICING TAPE FOR SPLICES IN J-BOX PER ART 110-3, 110-12, 110-14B N.E.C. 3.) GROUND J-BOXES PER ART 250 N.E.C. 4.) BOND BUSHING OR BODNING LCOKNUTS REQUIRED ASPER ART 250-94 N.E.C. 5.) GROUNDING SYSTEM FRO BOTHER SERVICES TO BE BONDED TOGETHER PER ART 230 AND 250 N.E.C. 6.) I.D. CIRCUIT BREAKERS IN NEW PANEL 7.) NEED VERIFICATION OF L-11 LICENSED CONTRACTOR DOING WORK AS REQUIRED BY AZ REGISTRAR OF CONTRACTORS.