Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABELS PER 230-7 N.E.C. AND 9287 CITY OF TUCSON ORDIN. 2.) USE U.L. LISTED SPLICING TAPE FOR SPLICES IN J-BOX PER ART 110-3, 110-12, 110-14B N.E.C. 3.) GROUND J-BOXES PER ART 250 N.E.C. 4.) BOND BUSHING OR BODNING LCOKNUTS REQUIRED ASPER ART 250-94 N.E.C. 5.) GROUNDING SYSTEM FRO BOTHER SERVICES TO BE BONDED TOGETHER PER ART 230 AND 250 N.E.C. 6.) I.D. CIRCUIT BREAKERS IN NEW PANEL 7.) NEED VERIFICATION OF L-11 LICENSED CONTRACTOR DOING WORK AS REQUIRED BY AZ REGISTRAR OF CONTRACTORS. |