Permit: T01EL01630

Parcel: 125150430

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL01630

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP.
07/06/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES #10 SCREWS/PLASTIC ANCHORS NOT ACCEPTABLE FOR ANCHORING OF SERVICE ENCLOSURE AND RISER CONDUIT,USE 1/4 MIN BLOTS, 110-3, 110-12 N.E.C 2.) SHEET METALF SCREW NOT APPROVED FOR GROUND LUG CONNECTION TO J-BOX ABOVE SERVICE , ALSO SCRAP OF ENAMER. 110-12, 250-96 N.E.C. 3.) INSTALL BOND BUSHING ON 2" CONDUIT FOR BRANCH CIRCUIT 250-94 N.E.C. OR BONDING LOCKNUTS.