Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/31/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 07/06/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES #10 SCREWS/PLASTIC ANCHORS NOT ACCEPTABLE FOR ANCHORING OF SERVICE ENCLOSURE AND RISER CONDUIT,USE 1/4 MIN BLOTS, 110-3, 110-12 N.E.C 2.) SHEET METALF SCREW NOT APPROVED FOR GROUND LUG CONNECTION TO J-BOX ABOVE SERVICE , ALSO SCRAP OF ENAMER. 110-12, 250-96 N.E.C. 3.) INSTALL BOND BUSHING ON 2" CONDUIT FOR BRANCH CIRCUIT 250-94 N.E.C. OR BONDING LOCKNUTS. |