Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/22/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/19/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) TIGHTEN HUB ON BOTTOM OF JUNCTION BOX. |
| 08/04/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) GROUND ROD'S TO BE MINIUM 6' APART 2.) NEED PERMANENT METAL ADDRESS LABELS 3.) USE APPROVED JUNCTION BOX OLD DISCONNECT NOT LISTED FOR USE AS JUNCTION BOX 4.) IDENTIFY NEUTRAL CONDUCTOR 5.) MISSING SCREW ON LB COVER 6.) FILL UNUSED OPENINGS AT PANEL. 7.) CONDUCTORS TO BE BLACK, RED, OR BLUE FOR HOT CONDUCTORS 8.) CONDUCTORS TO BE WHITE FOR NEUTRAL CONDUCTOR ENTIRE LENTH #8 & SMALLER. 9.) VERIFY LICENSED ELECTRICAL CONTRACTOR |