Permit: T01EL01612

Parcel: 131010480


Addresses:

5070 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR RECONNECT CALLED IN TO JUDY AM 6/26/01
06/25/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
06/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) INSTALL FUSES AT MAIN SERVICE 2,) INSTALL FUSES AT FRON BUILDING & LABEL DISCONNECT 2070 E 22ND FRONT" 3.) ISOLATE NEUT & GROUND FRONT BLDG GROUND TO GO TO LUG WITH #4 ON IT. CLEAN TERMINATION (WHERE #4 COPPER TIES, MUST USE BOLT & NUT TO CONNECT LUG TO FRAME AND CLEAN SURFACE BEHIND LUG. 4. FINISH REPAIRS IN BUILDING OPEN RECALL 5.) BOX COVER RECEPTACLES AROUND PNL