Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/26/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RECONNECT CALLED IN TO JUDY AM 6/26/01 |
| 06/25/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/22/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) INSTALL FUSES AT MAIN SERVICE 2,) INSTALL FUSES AT FRON BUILDING & LABEL DISCONNECT 2070 E 22ND FRONT" 3.) ISOLATE NEUT & GROUND FRONT BLDG GROUND TO GO TO LUG WITH #4 ON IT. CLEAN TERMINATION (WHERE #4 COPPER TIES, MUST USE BOLT & NUT TO CONNECT LUG TO FRAME AND CLEAN SURFACE BEHIND LUG. 4. FINISH REPAIRS IN BUILDING OPEN RECALL 5.) BOX COVER RECEPTACLES AROUND PNL |