Permit: T01EL01586

Parcel: 120052730

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T01EL01586

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2001 SIGN ELECTRIC Approved IVRS - Inspection 0000*
08/24/2001 SIGN ELECTRIC Denied IVRS - Inspection 0999*1.) TRANSFORMERS NEED TO BE BOLTED TO CANS TO COMPLETE BONDING CIRCUIT OR CONNECT A BONDING JUMPER FROM EQUIPMENT GROUND TO TRANFORMER BOX. 2.) ALL CONDUIT NIPPLES MUST BE WRENCH TIGHT. TIGHTEN LOCKNUTS @ TRANSFORMER BOXES. 3.) BOND PRIMARY J-BOX TO EQUIPMENT GROUND 4.) FLEXIBLE METAL CONDUIT MUST BE SECURED WITHIN 12" OF EACH TERMINATION AND FOR EVERY 3 1/2" OF LENGTH (SEE PRIMARY WIRING FROM 2 BOX @ SOUTH WALL.
08/23/2001 SIGN ELECTRIC Denied IVRS - Inspection 0999*1.) CERAMIC J-BOXES MAY NOT HANG FROM CONDUIT. 2.) TIGHTEN ALL CONDUIT NIPPLES. 3.) SECURE FLEX CONDUIT WITHIN 12" OF EACH TERMINATION AND FOR 4' IN LENGTH (UNLESS CONDUIT IS LESS THAN 3 1/2 IN LENGTH) 4.) SEAL ALL OPENINGS CUT THROUGH EXTERIOR WALL 5.) J-BOXES CONTAINING PRIMARY WIRING MUST BE BONDED TO GROUND. 6.) DO NOT ENERGIZE SIGN UNTIL SIGN ELECTRIC INSPECTION HAS BEEN APPROVED. 7.) IDENTIFY SIGN CIRCUITS AND CONTROLS IN ELEC. ROOM.
07/24/2001 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*