Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T01EL01586
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
08/24/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) TRANSFORMERS NEED TO BE BOLTED TO CANS TO COMPLETE BONDING CIRCUIT OR CONNECT A BONDING JUMPER FROM EQUIPMENT GROUND TO TRANFORMER BOX. 2.) ALL CONDUIT NIPPLES MUST BE WRENCH TIGHT. TIGHTEN LOCKNUTS @ TRANSFORMER BOXES. 3.) BOND PRIMARY J-BOX TO EQUIPMENT GROUND 4.) FLEXIBLE METAL CONDUIT MUST BE SECURED WITHIN 12" OF EACH TERMINATION AND FOR EVERY 3 1/2" OF LENGTH (SEE PRIMARY WIRING FROM 2 BOX @ SOUTH WALL. | |
08/23/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) CERAMIC J-BOXES MAY NOT HANG FROM CONDUIT. 2.) TIGHTEN ALL CONDUIT NIPPLES. 3.) SECURE FLEX CONDUIT WITHIN 12" OF EACH TERMINATION AND FOR 4' IN LENGTH (UNLESS CONDUIT IS LESS THAN 3 1/2 IN LENGTH) 4.) SEAL ALL OPENINGS CUT THROUGH EXTERIOR WALL 5.) J-BOXES CONTAINING PRIMARY WIRING MUST BE BONDED TO GROUND. 6.) DO NOT ENERGIZE SIGN UNTIL SIGN ELECTRIC INSPECTION HAS BEEN APPROVED. 7.) IDENTIFY SIGN CIRCUITS AND CONTROLS IN ELEC. ROOM. | |
07/24/2001 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000* |