Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 07/05/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 06/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) 2 GROUND RODS REQUIRED, COULD ONLY LOCATE 1. 250-52 NEC 2) INSTALL PERMANENT ADDRESS LABELS SCREWED PR RIVETED TO ENCLOSURE ART 230-70 NEC #9287 CITY ORD 3) STRAP GROUNDING ELECTRODE CONDUCTOR TO WALL 4) RE-SUPPORT RISERS, ANCHORS PULLLING OUT OF WALL, USE 1/4' MIN BOLTS, OR SHIELDS, #10 TO SMALL 5) INSTALL A GROUNDING ELECTRODE SYSTEM TO SECOND BLD OR ART 250-32. 250-52 NEC, AND RE-ATTACH GROUND SYSTEM IN DISC.SW. ALSO THE EXISTING DISC.SW. NEEDS TO BE APPROVED FOR OUTDOOR USE. 6) THE COOLER WIRING IS UNSAFE BLD "B" AND NEEDS TO BE ADDRESSED WITH OWNER. |