Permit: T01EL01580

Parcel: 110080690

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/12/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR.
07/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABEL SCREWED OR RIVITED TO SERVICE 230-70 NEC 9287 CITY ORDIN. 2.) STRAP GROUND WIRE ON WALL UP TO ROOF. 110-12 NEC. 3.) IT APPEARS SOMEONE TORE OFF ADDRESS TAG. INSTALL NEW ONE. 4.) BOND GAS PIPING 250-104 5.) SEAL ROOF PENETRATION AND NEC STRAP CONDUIT ON ROOF. 6.) HOW DID YOU RUN CONDUIT FROM ROOF TO SUB-PANEL
06/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*