Permit: T01EL01558

Parcel: 129052320


Addresses:

2908 E 17TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) ELECTRICAL CONDUIT FITTING USED INSIDE PANEL TO CONNECT THE CONDULET IS PROHIBITED BY NEC ART. 300. UNLOCK SUB PANEL. 2.) THE EXTENSION OF CIRCUITRY TO THE REMOTE STORAGE RM MUST BE DONE UNDER A SEPARATE PERMIT WHICH MUST INCLUDE THE STORAGE ROOM AS WELL. 3.) THE ADDITION OF THE PORCH ROOF MUST ALSO BE INCLUDED IN A NEW BUILDING PERMIT. THANKS.
07/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) THE GROUND AND NEUTRAL MUST BE SEPARATED AT THE SUB PANEL. 2.) THE NEUTRAL WIRE AT THE MAIN PANEL SHOULD BE RE-TERMINATED TO FIT IN ONE LUG HOLE OR TWO. DO NOT CUT STRANDS OF WIRE OFF TO MAKE FIT. 3.) USE THE PROPER CONNECTING THREADED FITTINGS ON THE CONDULETS. 4.) INSTALL BLANKS TO COVER EMPTY CIRCUIT BREAKER POSITIONS.
07/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) A RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF STILL NO ACCESS DUE TO DOG
06/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*IMPROPER FITTING USED AT LB INTO PANEL USE A CLOSED NIPPLE WITH A LOCK NUT ON INSIDE AND A LOCK NUT OUTSIDE 2.) SUPPORT 3/4" CONDUIT WITH IN 3' OF PANEL
06/18/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920*DOGS IN YARD. NO ONE AVAILABLE TO RESTAIN DOGS