Permit: T01EL01536

Parcel: 11921027E


Addresses:

2905 S MISSION RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/26/2001 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) SURFACE PLANER: DOUBLE LUGGING UNDER GROUND SCREW. USE GROUND BAR PROVIDED AND INSTALL BOND SCREW. 2.) THE ROGERS MODEL 91 EQUIPMENT IS WIRED WITH ROMEX. PLEASE USE THE APPROPRIATE SEALED BOXER AND WIRING METHODS. 3.) PLEASE CHECK LOOSE FITTINGS THROUGH OUT AND TABLE SAW CONDUIT NOT COMPLETELY FASTENED TO WALL, ALSO PLUMB CONDUIT. 4.) PLEASE WILL NEED APPROVED LETTER FOR CHANGING FIXTURE TYPE. (SEALED FIXTURE INSTALLED MEETS CODE) 5.) PLEASE I.D. CIRCUIT IN PANEL BOARD. PLEASE PROVIDE COPY OF LETTER FROM CONTRACTOR 6.) MUST INTERLOCK EQUIPMENT AS PER PLAN SEE PLAN NOTE. PLEASE COMPLY AND RECALL ASAP.