Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2001 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 06/13/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*1)NEED JUCTION BOX-CNANOT USE OLD DISCONNECT AS JUNCTION BOX.2)USE APPROVED FITTINGS TO CONNECT L.B.-CHASE NIPPLE NOT APPROVED.3)HIGHEST MEANS OF DISCONNECTING NOT TO BE OVER 6'7".4)BOND JUNCTION ENCLOSURE.5)STRAP BURY GROUND WIRES-OK TO PUT GROUND RODS FLUSH.6)PLEASE VERIFY LICENSED ELECRICAL CONTRACTOR. |