Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/14/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1)CAN NOT USE SHEET METAL SCREW FOR GROUNDING 250-8.2)CLEAN SURFACE UNDER LUG 250-12. |
| 06/12/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1. LABEL BREAKERS. 2. NEED BONDING DEVICE AT CONCENTRIC KNOCK OUTS. 3. BOND JUNCTION ENCLOSURE. |