Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2001 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 06/15/2001 | ELECTRIC - SERVICE UPGRADE | Denied | 1)INSTALL BOND BUSHINGS ON FEEDER CONDUITS. N.E.C. 250-94.2)LABEL SUB PANEL WITH PERMANENT LABEL.3)INSTALL CONNECTORS WITH BUSHED ENDS ON CONDUIT SLEEVES FOR CABLES TO PROTECT FROM ABRAISON 300-15C N.E.C. 300-16 4)INSTALL 1/4" BOLTS MIN. TO SUPPORT RISER, NOT DERYWALL SCREWS.5)BOND GAS PIPING 250-104 N.E.C. |