Permit: T01EL01487

Parcel: 125072940


Addresses:

445 N OLSEN AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/13/2001 ELECTRIC - SERVICE UPGRADE Approved
06/15/2001 ELECTRIC - SERVICE UPGRADE Denied 1)INSTALL BOND BUSHINGS ON FEEDER CONDUITS.
N.E.C. 250-94.2)LABEL SUB PANEL WITH PERMANENT LABEL.3)INSTALL CONNECTORS WITH BUSHED ENDS ON CONDUIT SLEEVES FOR CABLES TO PROTECT FROM ABRAISON 300-15C N.E.C. 300-16
4)INSTALL 1/4" BOLTS MIN. TO SUPPORT RISER, NOT DERYWALL SCREWS.5)BOND GAS PIPING 250-104 N.E.C.