Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/06/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*WILL CALL TEP OK TO CLEAR |
| 06/19/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1)NEED PERMANENT ADDRESS TAG-ENGRAVED METAL.2)STRAP GROUND WIRE TO WALL.3)BURY GROUND WIRE.4)BOND GAS/LINE.5)REMOVE OBSTRUCTION IN FRONT OF SERVICE (2X4) AND MAKE SMOOTH GRADE 30" WIDE X 36" OUT.6)DRIVE GROUND RODS FLUSH OR BELOW.7)ONLY ONE WIRE ON RID CLAMPS. |