Permit: T01EL01466

Parcel: 135042500

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/18/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
06/11/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1)NEED GROUNDING ELECTRODE SYSTEM-2 GROUND RODS MINIUM 6' APART.2)NEED WATER AND GAS BOND.3)NEED PERMANENT METAL APPRESS LABEL.4)LABEL BREAKERS.5)USE MANUFACTURE APPROVED BREAKERS.*TEP INSTALLED POWER WITHOUT CLEARANCE.*NOTE HOME OWNER DOING WORK.