Permit: T01EL01463

Parcel: 134070810


Addresses:

8342 E JULIA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/11/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR
06/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*PLEASE CALL FOR INSPECTION AGAIN WHEN SOMEONE WILL BE HOME
06/12/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1. THE GROUND CANNOT BE SPLICED WITH SPLIT BOLT CONNECTORS. YOU MUST USE CRIMP ON BUTT SPLICE FERRULES FOR CADWELD. 2. THE FEEDERS TO THE SPA MUST BE IN CONDUIT. 3. ROMEX IS NOT TO BE USED AS AN EXTENSION CORD. CONNECT IT TO A CIRCUIT BREAKER, NOT THE RECEPTACLE UNDER SUB PANEL. 4. THE SUB PANEL IS MOUNTED AT A HEIGHT WHICH CAUSES THE CIRCUIT BREAKERS TO BE ABOVE THE MAXIMUM 6'7" HEIGHT ALLOWED PER CODE, ART. 300. 5. THE MAIN PANEL IS NOT READILY ACCESSIBLE & A MAIN BREAKER WILL BE REQUIRED FOR THE SUB PANEL BREAKERS AT THE SUB PANEL.