Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR |
| 06/22/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*PLEASE CALL FOR INSPECTION AGAIN WHEN SOMEONE WILL BE HOME |
| 06/12/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1. THE GROUND CANNOT BE SPLICED WITH SPLIT BOLT CONNECTORS. YOU MUST USE CRIMP ON BUTT SPLICE FERRULES FOR CADWELD. 2. THE FEEDERS TO THE SPA MUST BE IN CONDUIT. 3. ROMEX IS NOT TO BE USED AS AN EXTENSION CORD. CONNECT IT TO A CIRCUIT BREAKER, NOT THE RECEPTACLE UNDER SUB PANEL. 4. THE SUB PANEL IS MOUNTED AT A HEIGHT WHICH CAUSES THE CIRCUIT BREAKERS TO BE ABOVE THE MAXIMUM 6'7" HEIGHT ALLOWED PER CODE, ART. 300. 5. THE MAIN PANEL IS NOT READILY ACCESSIBLE & A MAIN BREAKER WILL BE REQUIRED FOR THE SUB PANEL BREAKERS AT THE SUB PANEL. |