Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 06/14/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*1)GAS PIPING MUST BE BONDED.ART 250-104 N.E.C.2)GROUND RODS MUST BE 6' MIN. APART. ART 250 N.E.C. |