Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SERVICE UPGRADE APPROVED ONLY OK TO CLEAR OK CABLE DROP MECH INSPECTOR TO FOLLOW UP AC UNIT INSPECTION | |
| 06/04/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NO COMPLIANCE WITH ITEMS #2, AND #4.LAST INSPECTION ON 6/1/01. |
|
| 06/01/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1)IMPROPER WIRING METHOD AC WIRING.#8 ROMEX NOT APPROVED FOR 50 AMPS.2)3/4" CONDUIT TO BE STRAPPED,USE CLOSE NIPPLE WITH LOCKNUTS, BOND BUSHING, (LB) ART 250-94 N.E.C.3)USE MIN. 1/4 BOLTS TO ANCHOR RISER, #10 PLASTIC ANCHORS NOT ACCEPTABLE.4)PERMIT AND INSPECTION REQUIRED FOR NEW AC UNIT INSTALLATION.5)RE-CALL INSPECTION WHEN DONE.6)I.D. BREAKERS.(ALL) |