Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/31/2001 |
ELECTRIC - FINAL |
|
Denied |
1)PLEASE EXPOSE THE ENDS OF THE GROUND RODS DOWN TO THE CLAMP FOR INSPECTION.2)INSTALL PERMANENT ADDRESS ON SERVICE PANEL.3)CHECK W/TEP FOR POSSIBLE MIN-SPAN DROP.WIRING OVER ROOF WILL HAVE TO BE RAISED ABOVE ROOF TO MEET CODE REQUIRED CLEARANCE.SEE NEC ART. 230-SERVICES.4)ADD TWO SUPPORTS TO RISER CONDUIT.MINIMUM OF ONE WILL BE ACCEPTED. |