Permit: T01EL01306

Parcel: 123171830


Addresses:

1324 N VINE AV #02

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/04/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
05/29/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1)STRAP AND/OR BURY GROUNDING ELECTRODE CONDUCTOR.2)SEAL AROOUND RISER.3)WHAT IS INTENTSION OF OLD DICONNECT?4)SEAL ALL UNUSED OPENINGS-JUNCTION BOX.5)USE CORRECT BREAKERS AND LABEL CORRECTLY.